Windmill Cables
Halogen Free, Screened Control Cable 0.6/1 kV 90°C
Application:
These halogen-free, flame retardant cables are designed for frequency converter controlled AC drives, suitable for xed installation and occasional free exing indoors in dry, damp and wet conditions, as well as outdoors for low mechanical stress.
Standards:
DIN VDE 0250
IEC 60092-353
Construction:
Conductor: Stranded bare copper, class 5 according to DIN VDE 0295/IEC 60228.
Protective Conductor: Stranded bare copper, class 5 according to DIN VDE 0295/IEC 60228. For cross sections > 16mm² the protective conductor is divided into 3 cores.
Insulation: Halogen free special XLPE according to IEC 60502-4.
Screen: Al coated tape + tinned copper wires braid.
Sheath: Halogen free compound HM4. Halogen free PUR can be offered upon request.
Technical Data:
Rated Voltage Uo/U (Um):600/1000V
Operating Temperatures:-5℃~+90℃
Minimum Bending Radius:flexing: 20×OD; fixed: 10×OD
Flame Retardant:IEC 60332-3
Halogen Free:IEC 60754
Gases Corrosively:IEC 60754
Ozone Resistant:Yes
UV Resistant:Yes
Dimensions and Weight:
Construction | Nominal Overall Diameter | Nominal Weight |
---|---|---|
No. of cores×mm² | mm | kg/km |
4×1.5 | 11.0 | 230 |
4×2.5 | 12.5 | 300 |
4×4 | 15.5 | 390 |
4×6 | 17.5 | 420 |
4×10 | 19.5 | 780 |
3×16+3×2.5 | 22.5 | 820 |
3×25+3×4 | 26.0 | 1150 |
3×35+3×6 | 29.5 | 1550 |
3×50+3×10 | 35.0 | 2400 |
3×70+3×10 | 38.5 | 3100 |
3×95+3×16 | 44.0 | 4200 |
3×120+3×16 | 48.0 | 4630 |
3×150+3×25 | 53.0 | 5880 |
3×185+3×35 | 58.0 | 7200 |
3×240+3×50 | 66.0 | 9600 |
3×300+3×50 | 73.0 | 11530 |